Rơ le giám sát mạch cắt

Model  VDF-10 VDJ-30
Applications Trip circuit supervision for single-phase circuit breakers Trip circuit supervision for three-phase circuit breakers
Construction characteristics  
Timing Contacts no. 2 Changeover 2 Changeover
Options With OP options. See model selection table. Options are not available
Weight (g) 100 163
Dimensions (mm) (A) 42.5 x (B) 50.4 x (C) 96.6   (F large Type) (A) 82.5 x (B) 50.4 x (C) 96.6   (J large Type)
Coil characteristics    
Standard voltages(1)  24/30, 60, 110/125, 220 Vdc, 110/127, 230 Vac (50-60 Hz) 24/30, 60, 110/125, 220 Vdc
Voltage range +10% -25% UN
Pick-up voltage (23° C) 70% UN
Release voltage (23° C) 60% UN
Consumptions 1.35 W 1.6 W
Operating time  
Drop-out time >500 ms
Contacts   
Contact material AgNi
Permanent current 8 A
Instantaneous current 15 A
Max. making capacity 15 A during 4 s
Max. breaking capacity 0.3 A / 110 Vdc
Umax opened contac 250 Vdc / 400 Vac
Performance data  
Mechanical endurance  10 million operations
Operating temperature -40°C +55°C
Storage temperature -40°C +85°C
Max. operating humidity  93% / +40°C
Operating altitude(2)  <2000 m
(1) Other voltage upon request
(2) Ask for higher altitudes
zalo-icon
facebook-icon
phone-icon
zalo-icon
facebook-icon
phone-icon